ABB Low Voltage Drives DCS800-S02-0450-05 MODULE DRIVE 4-QUADRANT (REVERSING), Product Family: DCS800, Horsepower: 100 HP @ 230…
Alternate Item Number: 3AUA0000013769
UPC: 662348074749
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 4-Quadrant (Reversing) DC Drive Module
- 100 HP @ 230 VAC / 250 HP @ 460 VAC
- 385 A @ 240 VDC / 428 A @ 500 VDC Output Current
- UL TYPE OPEN (IP00) Enclosure for Wall-Mounting
- 3-Phase AC Input, Precise Motor Control
Specifications
Current Rating | 385 A @ 240 VDC / 428 A @ 500 VDC |
IP Rating | IP00 |
Mounting Type | Wall-mount |
Series | DCS800 |
Size | 18.1 in x 10.6 in x 12.2 in |
Voltage Rating | 230 VAC/240 VDC & 460 VAC/500 VDC |
Package Dimensions (L x W x H) | 21 in x 15 in x 15 in |
Package Dimensions (L x W x H) | 53.34 cm x 38.1 cm x 38.1 cm |
Package Weight (Imperial) | 62.000 L |
Package Weight (Metric) | 28.123 kg |

DCS800-S02-0450-05+L508
MODULE DRIVE 4-QUADRANT (REVERSING), Product Family: DCS800, Horsepower: 100 HP @ 230 VAC / 250 HP @ 460 VAC, Output Current: 385 A @ 240 VDC / 428 A @ 500 VDC, Voltage: 230 VAC/240 VDC & 460 VAC/500 VDC, UL TYPE OPEN (IP00), Mounting: Wall-mount, DDCS Communications Board, 3-Phase Input, Frame: D3, Product HxWxD: 18.1 in x 10.6 in x 12.2 in, Product Weight: 55 lbs
DCS800-S02-0680-05+S171
MODULE DRIVE 4-QUADRANT (REVERSING), Product Family: DCS800, Horsepower: 150 HP @ 230 VAC / 400 HP @ 460 VAC, Output Current: 647 A @ 240 VDC / 647 A @ 500 VDC, Voltage: 230 VAC/240 VDC & 460 VAC/500 VDC, UL TYPE OPEN (IP00), Mounting: Wall-mount, 120 VAC Fan Voltage, 3-Phase Input, Frame: D4, Product HxWxD: 25.4 in x 10.6 in x 13.6 in, Product Weight: 84 lbs
DCS800-S02-0680-05+S171+L508
MODULE DRIVE 4-QUADRANT (REVERSING), Product Family: DCS800, Horsepower: 150 HP @ 230 VAC / 400 HP @ 460 VAC, Output Current: 647 A @ 240 VDC / 647 A @ 500 VDC, Voltage: 230 VAC/240 VDC & 460 VAC/500 VDC, UL TYPE OPEN (IP00), Mounting: Wall-mount, DDCS Communications Board, 120 VAC Fan Voltage, 3-Phase Input, Frame: D4, Product HxWxD: 25.4 in x 10.6 in x 13.6 in, Product Weight: 84 lbs
DCS800-S02-0820-05+L508+S171
MODULE DRIVE 4-QUADRANT (REVERSING), Product Family: DCS800, Horsepower: 200 HP @ 230 VAC / 500 HP @ 460 VAC, Output Current: 780 A @ 240 VDC / 806 A @ 500 VDC, Voltage: 230 VAC/240 VDC & 460 VAC/500 VDC, UL TYPE OPEN (IP00), Mounting: Wall-mount, DDCS Communications Board, 120 VAC Fan Voltage, 3-Phase Input, Frame: D4, Product HxWxD: 25.4 in x 10.6 in x 13.6 in, Product Weight: 84 lbs
DCS800-S02-0820-05+S171
MODULE DRIVE 4-QUADRANT (REVERSING), Product Family: DCS800, Horsepower: 200 HP @ 230 VAC / 500 HP @ 460 VAC, Output Current: 780 A @ 240 VDC / 806 A @ 500 VDC, Voltage: 230 VAC/240 VDC & 460 VAC/500 VDC, UL TYPE OPEN (IP00), Mounting: Wall-mount, 120 VAC Fan Voltage, 3-Phase Input, Frame: D4, Product HxWxD: 25.4 in x 10.6 in x 13.6 in, Product Weight: 84 lbs
DCS800-S02-0820-05+L508+S199
MODULE DRIVE 4-QUADRANT (REVERSING), Product Family: DCS800, Horsepower: 200 HP @ 230 VAC / 500 HP @ 460 VAC, Output Current: 780 A @ 240 VDC / 806 A @ 500 VDC, Voltage: 230 VAC/240 VDC & 460 VAC/500 VDC, UL TYPE OPEN (IP00), Mounting: Wall-mount, DDCS Communications Board, Drive-to-drive Communication Board, 3-Phase Input, Frame: D4, Product HxWxD: 25.4 in x 10.6 in x 13.6 in, Product Weight: 84 lbs
DCS800-S02-0200-05+K462
MODULE DRIVE 4-QUADRANT (REVERSING), Product Family: DCS800, Horsepower: 50 HP @ 230 VAC / 100 HP @ 460 VAC, Output Current: 190 A @ 240 VDC / 190 A @ 500 VDC, Voltage: 230 VAC/240 VDC & 460 VAC/500 VDC, UL TYPE OPEN (IP00), Mounting: Wall-mount, ControlNet Adapter, 3-Phase Input, Frame: D2, Product HxWxD: 14.6 in x 10.6 in x 10.6 in, Product Weight: 35 lbsFrequently Asked Questions
What is the enclosure rating of the DCS800-S0x power converter module?
The module has a NEMA TYPE OPEN (IP00) rating and requires mounting in a protective enclosure.
What is the maximum output voltage for a 4-Q drive with 230V AC input?
The maximum output voltage for a 4-Q drive with 230V AC input is 310V.
What is the maximum output voltage for a 4-Q drive with 400V AC input?
The maximum output voltage for a 4-Q drive with 400V AC input is 540V.
What is the maximum output voltage for a 4-Q drive with 690V AC input?
The maximum output voltage for a 4-Q drive with 690V AC input is 930V.
What is the maximum output voltage for a 4-Q drive with 990V AC input?
The maximum output voltage for a 4-Q drive with 990V AC input is 1350V.
When should I use a non-reversing (2-Q) drive?
Use a 2-Q drive when motor torque and speed are always in the same direction and significant stopping power is not needed, like for fans or pumps.
What are the limitations of a 2-Q drive?
A 2-Q drive cannot slow down an inertial load or reverse direction unless field reversal is used.
When are reversing (4-Q) drives used?
4-Q drives are used when motor torque can occur in either direction, such as for conveyors, cranes, or rolling mills.
What is the Short Circuit Current Rating (SCCR) for D1-D4 frame sizes?
The SCCR for frame sizes D1 through D4 is 65 kA.
What is the SCCR for D5-D7 frame sizes?
The SCCR for frame sizes D5 through D7 is 100 kA.