
ABB Low Voltage Drives ACS800-37-0780-5+B054+C129+H359+K458 CABINET DRIVE ULTRA LOW HARMONIC, Product Family: ACS800, Horsepower: 700 HP, Output…
Alternate Item Number: 3AUA0000021882
UPC: 662348055434
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 700 HP, 856A output current, 480VAC voltage rating (380-500V input range)
- NEMA 1/UL Type 1 filtered enclosure (IP42) for harsh environments
- Ultra-low harmonic distortion (Ithd ~4.5%) reduces electrical interference
- Floor-mounted design with local/remote LCD display and keypad
- ModBus adapter for industrial automation system integration

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What is the standard protection class for the ACS800-37?
The standard protection class for the ACS800-37 is UL Type 1.
Does the ACS800-37 include a built-in low harmonic filter?
Yes, it features a built-in low harmonic LCL filter.
What motor control technology does the ACS800-37 use?
It utilizes ABB's exclusive Direct Torque Control (DTC) for speed and torque control.
What is the purpose of the ACS800-37 drive?
The ACS800-37 drive is designed to eliminate low and high order harmonics, meeting strict standards like IEEE519 without external filtering equipment.
What is the maximum altitude for operation without derating?
The drive can operate up to 1000 meters without derating.
What is the relative humidity limit for operation?
The relative humidity must be between 5% and 95%, with no condensation allowed.
How does the ACS800-37 compare to external harmonic solutions?
It is simpler, more compact, and offers better harmonic performance than 12- and 18-pulse solutions, avoiding the need for dedicated multi-pulse transformers.
What is the operating temperature range for the ACS800-37?
The operating temperature range is -15 to +50°C, with reduced output current above 40°C.
What are the available supply voltage ranges for the ACS800-37?
It supports 3-phase supply voltages of 208-240V, 380-500V, and 525-690V.
Can the ACS800-37 handle AC line voltage imbalances?
Yes, it is impervious to AC line voltage imbalances up to and over 3%.
















