- 250 HP, 302 A output current for high-power industrial applications
- Ultra-low harmonic distortion for clean power quality
- NEMA 12/IP54 enclosure for protection in harsh environments
- Local or remote LCD display and keypad for flexible control
- DeviceNet adapter for seamless integration with automation systems

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What is the primary function of the ACS800-37 drive?
The ACS800-37 drive is designed to eliminate low and high order harmonics, providing a low harmonic solution that meets stringent power quality standards like IEEE519.
Does the ACS800-37 require external filtering equipment?
No, the ACS800-37 drive has an incorporated active converter and LCL line filter, eliminating the need for additional external filtering equipment or multi-pulse transformers.
What protection class does the standard ACS800-37 offer?
The standard ACS800-37 drive offers UL Type 1 protection class.
What are the available supply voltage ranges for the ACS800-37?
The drive supports 3-phase supply voltages of 380, 400, 415, 460, 480, 500 V, and also 525, 550, 575, 600, 690 V.
What is the Short Circuit Current Rating (SCCR) for the ACS800-37?
The SCCR for ACS800-37 models is 100kA for models PC, U2, U7/07, 17, and 37.
What motor control technology does the ACS800-37 use?
The ACS800-37 utilizes ABB's exclusive Direct Torque Control (DTC) for accurate speed and torque control.
What is the power factor of the ACS800-37 drives?
ACS800-37 drives with fundamental power factor 1 (cosϕ1 = 1) have a total power factor (cosϕ) of 0.99.
What are the dimensions of the R8i frame size for UL Type 1 enclosure?
The R8i frame size with UL Type 1 enclosure has a width of 48.4 inches, a height of 83.9 inches, and a depth of 25.4 inches.
What is the efficiency of the ACS800-37 drives?
The efficiency for ACS800-U11, -17, -U31, and -37 models is 97% at nominal power.
How does the ACS800-37 compare to external harmonic solutions?
The ACS800-37 is simpler, more compact, and offers better harmonic performance than 12- and 18-pulse external solutions, also operating with a unity power factor.