ABB Low Voltage Drives ACS800-17-0400-7+B054+C129+M604+Q951 CABINET DRIVE REGENERATIVE, Product Family: ACS800, Horsepower: 300 HP, Output Current…
Alternate Item Number: 3AUA0000021884
UPC: 662348052334
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 300 HP (322 A) regenerative AC drive for high-performance applications
- Active supply unit enables energy regeneration back to AC line, reducing waste heat
- UL Type 1 (IP42) filtered enclosure for floor-mounted installations
- Built-in LCL line filter, EMC filter, and main disconnect switch with aR fuses
- Programmable I/O, galvanically isolated inputs, and multilingual control panel
Specifications
Connection Type | 3-phase |
Current Rating | 322 A |
IP Rating | IP42 |
Mounting Type | Floor-mounted |
NEMA Rating | Type 1 |
Series | ACS800 |
Size | 91.1 in x 48.4 in x 25.4 in |
Voltage Rating | 575 VAC |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What is the operating temperature range for the ACS800-17 drive?
The drive can operate in ambient temperatures from -15 to +50°C, with reduced output current above 40°C.
What supply voltages are compatible with the ACS800-17 drive?
The drive supports 3-phase supply voltages of 208-240V, 380-500V, and 525-690V.
What is the standard degree of protection for the ACS800-17?
The standard degree of protection for the ACS800-17 is UL Type 1.
What motor control method does the ACS800-17 use?
The ACS800-17 utilizes ABB's exclusive Direct Torque Control (DTC) for motor control.
What is the Short Circuit Current Rating (SCCR) for the ACS800-17?
The SCCR for the ACS800-17 is 100kA.
Does the ACS800-17 have built-in harmonic filtering?
Yes, it has a built-in LCL line filter and EMC filter as standard features.
What is the efficiency rating of the ACS800-17?
The efficiency rating for the ACS800-17 is 97% at nominal power.
What is the maximum output frequency of the drive?
The output frequency can range from 0 to ±300 Hz.
What is the power factor for the ACS800-17?
The power factor is cosϕ1 = 1 (fundamental) and cosϕ = 0.99 (total).
Can the ACS800-17 operate at altitudes above 1000 meters?
Yes, it can operate up to 4000 meters, but with derating of approximately 1% for every 100 meters above 1000m.