ABB - Low Voltage Drives ACS800-17-0170-5+B054+C129+L505+M602 - CABINET DRIVE REGENERATIVE, Product Family: ACS800, Horsepower: 150 HP, Output Current: 192 A, Voltage: 480 VAC, Voltage Range: 380-500V, NEMA 1 / UL Type 1 Filtered (IP42), Floor-mounted, Local or Remote Mounted LCD Display and Keypad, Thermistor Relay (1), 0170 KVA, 3-Phase Input, 3-Phase Output, Frame: R7i, Product HxWxD: 91.1 in x 24.8 in x 25.4 in, Product Weight: 882 lbs

ABB Low Voltage Drives ACS800-17-0170-5+B054+C129+L505+M602 CABINET DRIVE REGENERATIVE, Product Family: ACS800, Horsepower: 150 HP, Output Current…

Alternate Item Number: 3AUA0000034927

UPC: 662348051306


Documents & Media
Specification Sheet

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

ABB ACS800-17-0170-5+B054+C129+L505+M602 is a cabinet-built regenerative AC drive for high-demand industrial applications requiring energy recovery and precise motor control. Rated 150 HP (112 kW), it delivers 192A output current at 480VAC and operates efficiently within a 380-500VAC input range. The integrated active supply unit enables full power flow in both motoring and regenerating modes, returning braking energy to the AC line network instead of dissipating it as heat, eliminating the need for external braking resistors or mechanical brakes. The drive features a compact R7i frame with dimensions of 91.1" x 24.8" x 25.4" and weighs 882 lbs, designed for floor-mounted installation. Standard features include a main disconnect switch with aR fuses, line contactor, coated circuit boards, and a long-lifetime cooling fan and capacitors. The alphanumeric multilingual control panel with start-up assistant simplifies configuration. Key applications include material handling systems, elevators, cranes, and processes requiring frequent acceleration/deceleration. The patented DTC motor control enables fast transitions between motoring and generating modes while maintaining full motor voltage even during line voltage drops. Additional options include ATEX motor protection, cabinet heaters, fieldbus modules, emergency stop interfaces, and multiple thermistor/PT100 relays for comprehensive motor protection. The NEMA 1 / UL Type 1 (IP42) enclosure provides basic protection against dust and moisture, suitable for general industrial environments. With 3 I/O and fieldbus extension slots, the ACS800-17 supports extensive programmability and integration into automation systems. The drive's regenerative capability delivers measurable energy savings compared to traditional braking methods, particularly in applications with high braking duty cycles. For demanding environments requiring enhanced protection, UL Type 12 filtered enclosures are available as an option.
  • 150 HP (112 kW) regenerative drive with 192A output current at 480VAC
  • Active supply unit enables energy recovery during braking, reducing heat dissipation
  • Compact R7i frame: 91.1" H x 24.8" W x 25.4" D, 882 lbs floor-mounted design
  • Patented DTC motor control with fast motoring/generating transitions and voltage drop compensation
  • Includes thermistor relay and 0170 KVA rating for efficient thermal management
Double plastic fiber optic, Qty 1, 5 meters long

61059113

Double plastic fiber optic, Qty 1, 5 meters long
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.

FENA-21

The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.
600V Class Iron Core Reactor, Core and Coil, 11 Amps, 2.57 Inductance, 60 Hz

CRX0011AC

600V Class Iron Core Reactor, Core and Coil, 11 Amps, 2.57 Inductance, 60 Hz
KDR, 208V, 19A, 5HP

KDRB22L

KDR, 208V, 19A, 5HP

Frequently Asked Questions

What is the power range for the ACS800-17 series?

The ACS800-17 series offers a power range from 125 to 2600 Hp.

What type of protection class does the ACS800-17 have as standard?

The standard protection class for the ACS800-17 is UL Type 1.

What motor control method does the ACS800-17 use?

The ACS800-17 utilizes ABB's exclusive Direct Torque Control (DTC) method.

Does the ACS800-17 require external braking devices?

No, the ACS800-17 includes a complete regenerative drive package and does not require external braking devices.

What is the paint color of the ACS800-17 enclosure?

The paint color for the ACS800-17 is Light beige RAL 7035 semi-gloss.

What is the operating temperature range for the ACS800-17?

The operating temperature range is -15 to +50°C, with reduced output current above 40°C.

What is the maximum altitude for operation without derating?

The drive can operate up to 1000 meters without any derating.

What is the relative humidity limit for operation?

The relative humidity must be between 5 to 95%, with no condensation allowed.

What are the standard supply voltages for the ACS800-17?

Standard supply voltages are 3-phase, 380, 400, 415, 460, 480, 500 Vac, and 525, 550, 575, 600, 690 Vac.

What is the Short Circuit Current Rating (SCCR) for the ACS800-17?

The SCCR for ACS800-17 is 100ka.