ABB Low Voltage Drives ACS550-PC-368A-4 GENERAL PURPOSE PACKAGED DRIVE W/ CIRCUIT BREAKER DISCONNECT, Product Family: ACS550…
Alternate Item Number: 3AUA0000013658
UPC: 662348043301
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 300 HP (200 kW) motor rating
- 368 A output current
- 480 VAC nominal voltage (380-480V range)
- NEMA 1 / UL Type 1 (IP21) enclosure
- Free-standing mounting with circuit breaker disconnect

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What are the voltage and power ranges for ABB standard drives?
The drives support 3-phase input power from 208 to 240 V (0.75-100Hp), 380 to 480 V (1-550Hp), and 500 to 600 V (1.5-150Hp).
What is the operating frequency range for motor connection?
The motor connection frequency range is from 0 to 500 Hz.
What are the acceleration and deceleration time limits?
Acceleration and deceleration times can be set between 0.1 to 1800 seconds.
What types of analog inputs are available?
There are two analog inputs that accept voltage signals (0-10 V) or current signals (0-20 mA).
What is the auxiliary voltage provided by the drive?
The drive provides an auxiliary voltage of 24 V DC ±10%, with a maximum current of 250 mA.
How many digital inputs does the drive have?
The drive is equipped with six digital inputs that accept 12 V to 24 V DC.
What are the specifications for the relay outputs?
There are three relay outputs with a maximum switching voltage of 250 V AC/30 V DC and a maximum switching current of 6 A.
What serial communication protocol is built-in?
The drive has a built-in Modbus RTU protocol for serial communication via RS 485.
What is the recommended ambient temperature range for operation?
The ambient temperature range for operation is 15 to 40°C (5 to 104° F).
What is the maximum relative humidity for the drive?
The relative humidity should be lower than 95%, without condensation.