ABB Low Voltage Drives ACS355-03U-06A7-2+B063 ACS355 AC Drive, 3-200-240V In, 1.5HP, 6.7A, Type 4X, 1.5 overload, Blank, HxWxD…
Alternate Item Number: 3AUA0000058133
UPC: 662348022306
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- ABB ACS355 AC Drive, SKU ACS355-03U-06A7-2+B063
- 1.5 HP (1.1 kW) motor output
- 6.7 Amp continuous current rating
- 200-240 VAC input voltage
- IP66/UL Type 4X enclosure for robust protection
- Compact dimensions: 12.01" H x 7.28" W x 11.06" D
- Designed for pump and fan applications
- 1.5 overload capability
Specifications
1.5 | HP |
11.06 | in |
12.01 | in |
16.98 | lb |
200-240 | VAC |
240 | VAC |
3-Phase | A |
6.7 | A |
7.28 | in |
Amerage | 6.7 A |
Control Panel | Blank |
Current Rating | 6.7 A |
Frame Size | R1 |
Height | 12.01 in |
Horsepower | 1.5 HP |
Horsepower 10% & 50% Overload/ 1 min | 1.5 HP |
Input Phase | 3-Phase |
IP Rating | IP66 |
Length | 11.06 in |
Mounting | Wall |
Mounting Type | Wall |
Nema Rating | Type 4X |
Number of Phases Input | 3 |
Number of Phases Output | 3 |
Output Current | 6.7 A |
Output Current 10% & 50% Overload/ 1 min | 6.7 A |
Output Phase | 3-Phase |
Phases | 3-Phase A |
Series | ACS355 |
Size | 12.01x7.28x11.06 in |
Type | ACS355 Drive |
UL Type | 4X |
Voltage | 240 V |
Voltage Range | 200-240 V |
Voltage Rating | 3-200-240 VAC |
Voltage Rating | 240 Vac |
Weight | 16.98 lb |
Width | 7.28 in |
Package Dimensions (L x W x H) | 11.06 IN x 7.28 IN x 12.01 IN |
Package Dimensions (L x W x H) | 28.0924 cm x 18.4912 cm x 30.5054 cm |
Package Weight (Imperial) | 16.980 L |
Package Weight (Metric) | 7.702 kg |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What are the dimensions of the ACS355-03U-06A7-2 + B063 model?
The dimensions for the IP66/UL Type 4X model ACS355-03U-06A7-2 + B063 are 12.0 in height, 7.7 in width, and 11.1 in depth.
What are the available AC supply voltage and power ranges?
It supports 1-phase (200-240V, 0.37-2.2kW), 3-phase (200-240V, 0.37-11kW), and 3-phase (380-480V, 0.37-22kW).
What are the available fieldbus connection options?
Fieldbus connections are available via optional modules including PROFIBUS DP, CANopen®, DeviceNetTM, Modbus, Ethernet, Profinet/etherCAT®, and LonWorks®.
What is the operating temperature range for the ACS355 drive?
The drive operates in ambient temperatures from -10 to 40°C (14 to 104°F), with derating at 50°C (122°F).
Can the ACS355 drive be preconfigured without power?
Yes, the drive can be preconfigured in seconds without powering it using the FlashDrop tool.
What are the programmable digital input capabilities?
It has five digital inputs that accept 12 to 24 V, PNP and NPN, with DI5 programmable for 0 to 16 kHz pulse train.
Does the ACS355 drive have a safe torque-off function?
Yes, the Safe Torque Off function (SIL 3) is included as standard on the ACS355 drive.
What is the overload capacity of the ACS355 drive?
The drive has an overload capacity of 1.5 x I2N for 1 minute every 10 minutes, and 1.8 x I2N for 2 seconds at start.
What is the maximum output frequency of the ACS355 drive?
The ACS355 drive has a maximum output frequency of 600 Hz.
What is the maximum humidity for operation?
The drive can operate in relative humidity lower than 95%, provided there is no condensation.